Battery sizing

Usable battery capacity: how much of 1 kWh you get

A 1,000 Wh battery stores a nominal kilowatt-hour. The useful question at a desk is how many hours of work that delivers through the chosen outlet.

Pick a reasonable range

Home Power Index starts steady AC estimates at 80% usable energy. Jackery uses the same fraction in a planning example. It is an assumption you can change. The inverter, its own operating draw, battery condition and the appliance load all affect delivery. When deciding between close model sizes, calculate the result with a lower fraction as well. A backup plan that works across both estimates has more room for variation.

Worked example

A difference that can change the size you buy

A 1,024 Wh unit powering a 90 W office setup for eight hours needs 720 Wh at the outlet. From full, an 80% allowance gives 819 Wh and about 9.1 hours. A 70% allowance gives 717 Wh and just under eight hours. A small efficiency assumption can decide whether you finish the session.

Start with the battery you will actually have

A station put away at less than full charge begins the next session with a smaller budget. Multiply nominal capacity by the share of charge you intend to use, then by the assumed delivered fraction. If you want a reserve at the end, subtract it in percentage points of the full battery. For an 80% start and a 20% finish, you can budget 60% of nominal capacity before losses.

Know where you measured

An AC plug meter gives a load-side reading. If you have already measured delivered Wh during an actual discharge of that same station, that figure already includes the losses for that setup. Applying the generic usable fraction a second time would reduce the estimate twice. Keep the test load, output mode and temperature beside that measurement.